Default Configuration

ParameterDefault ValuePurpose
Measurement interval300 s (5 minutes)Distance sampling frequency
Report interval3600 s (1 hour)Heartbeat if no change detected
Ranging modeShort range (40–1300 mm)Default measurement range
Ranging timing budget50 msBalance between accuracy and power
Ranging ROIX1=4, Y1=4, X2=11, Y2=11Default beam width
AccelerometerDisabledOptional tilt detection
TemperatureDisabledOptional temperature reporting
Network roleRoutingParticipates in mesh routing

Configurable Parameters

Measurement and Reporting Intervals

ParameterRangeDefaultImpact
Measurement interval10 s – 24 h300 s (5 min)How often the sensor measures distance
Report interval600 s – 24 h3600 s (1 hour)How often the sensor reports when no change detected

Battery life impact:

Measurement IntervalExpected Battery Life
1 minuteUp to 3 years
5 minutes (default)Up to 4 years
15 minutesUp to 5 years

Ranging Mode

ModeRangeBest For
Short range (1)40–1300 mmDispensers, small bins, shelves
Long range (2)Up to 4000 mmLarge bins, tanks, tall containers

Use short range for better accuracy when the target is within 1.3 m. Switch to long range only when measuring distances above 1300 mm.

Ranging Timing Budget

Controls the trade-off between measurement accuracy and power consumption.

Short range values: 15, 20, 33, 50, 100, 200, 500 ms Long range values: 20, 33, 50, 100, 200, 500 ms

  • Lower values (15–33 ms): Faster, lower power, more noise
  • Default (50 ms): Balanced accuracy and power
  • Higher values (100–500 ms): Best accuracy, higher power consumption

Ranging ROI (Region of Interest)

Controls the beam width and direction using a 16×16 sensor matrix (coordinates 0–15).

ParameterRangeDefaultDescription
X10–154Left boundary
Y10–154Top boundary
X20–1511Right boundary
Y20–1511Bottom boundary
  • Default (4,4,11,11): Standard beam width (~21°)
  • Wider ROI (2,2,13,13): Broader detection cone (~27°)
  • Narrower ROI (6,6,9,9): Focused beam (~15°)
  • Minimum size: 4×4 matrix (e.g., 6,6,9,9)

Adjust ROI to match the target size and installation geometry.

Optional Sensors

These sensors are disabled by default but can be enabled via support:

SensorValuesUse Case
Accelerometer0=disabled, 1=enabledDetect sensor tilt or tampering
Temperature0=disabled, 1=enabledMonitor ambient temperature alongside distance

Network Role

RoleDescription
Routing (default)Sensor participates in Wirepas mesh routing for other devices
Non-routingSensor only transmits its own data (lower power, but reduces mesh coverage)

Requesting Configuration Changes

Contact support@haltian.com with:

  • Sensor IDs (vendor serial numbers)
  • Parameters to change
  • Desired values
  • Use case context (helps support recommend optimal settings)

Configuration changes are delivered remotely via the Wirepas mesh network. Changes take effect on the next sensor uplink (typically within the current measurement interval).