Rooms
How meeting rooms are used, by how many people, and how their air is
Overview
Rooms shows how meeting rooms, phone booths and other spaces are used and how their air is: which rooms were used, how much each was used, how many people each room held, and the CO₂, temperature and humidity in each room. A device is part of Rooms when it carries the keyword room or rooms in Haltian Studio.

The Rooms dashboard, with demo data
Who it helps
| Person | What they get |
|---|---|
| Workplace manager | Which rooms stood empty and which were used most, to decide where more rooms, or fewer, are needed |
| Facility manager | CO₂, temperature and humidity room by room, and how long each room spent at 900 ppm CO₂ or more |
| Office team | Which rooms were used and how much, on the floor plan, and when the rooms are usually busy |
Views
| View | What you see |
|---|---|
| Dashboard | How many of the rooms were used in the period. The floor plan with each room as Used, Not used or No data, and the floor’s zones as named outlines. A card per room with its share of time in use. Tiles for Most rooms in use at once, Time in use and the most people seen. The occupied share by hour or by day, and the most and least used rooms |
| Time in use | The share of time each room was in use, the least used room, the rooms never used, and the rooms under 80 % known. One bar per room, most used first |
| Patterns | A weekday-by-hour grid of the in-use share for all rooms, with the busiest and the quietest hour |
| People | The people count over time, for every room that counts people or for one room, and the highest count per hour or day |
| A room’s page | Opened from a room’s card, its name in the ranking, or its bar in Time in use. Time in use, Most people and Median when in use, a timeline of the chosen day’s in-use and free periods, the room’s own weekly pattern, and its air quality |
| Air quality | CO₂, temperature and humidity over the period, one line per room. The CO₂ chart has reference lines at 750 and 900 ppm, the WELL v2 ventilation levels. A By room table with the mean, the highest reading and the time at 900 ppm or more, TVOC included |
| Rooms | Every device tagged room in the space, with where it is, its Last reading before midnight, its readiness (Ready, Partial or Absent) and when it was last seen |
| Export | How a report is exported: the two formats, which reports can be exported, and that there are no scheduled or emailed reports. Each report exports itself from its own page |
| Settings | Which devices are included, what makes a device ready, the space scope, and your office hours |
All reports use the period bar and can be exported.
Key terms
- In use — from the room’s occupancy sensor. With a presence sensor only, the room is in use from a report of movement until the next report of none, and the page says “movement detected”, not a people count.
- Used — the room was in use at any time in the period’s hours. Not used means its known time held no use.
- Time in use — the share of the known available time a room was in use. It is not utilization proper, which also takes how full the room was.
- Median when in use — the middle people count while anyone is in the room, so it says how full the room is when it is used.
Set up in Haltian Field and Haltian Studio
- In Haltian Field, install each device in a space: site, building and floor.
- Add the keyword
roomorroomsto the device, in Haltian Studio or Haltian Field. - In Haltian Studio, give the floor a floor plan image and a position. In Haltian Field, place the device on that floor plan when you install it. A device with no position is named below the plan instead of drawn on it.
- For a people count, tag a device that counts people, such as a device group of people sensors. A Thingsee PRESENCE sensor on its own shows movement detected, not a count.
- For air quality, tag the room’s air sensor as well.
- In Haltian Studio, draw and name the room’s zone on its floor to see the room outlined on the floor plan.
Good to know
- A device that measures only air quality shows in Air quality and on the Dashboard cards, not in Time in use, Patterns or People. In the Rooms list its readiness is Absent.
- Settings are read-only, except for office hours.
- The air-quality lines are levels to read against, not a grade.
Try it
- Select a building or floor in the space selector and open Rooms.
- On Dashboard, see on the floor plan which rooms were used yesterday.
- Choose This week and Compare to previous, then open Time in use to see the least used rooms and the change from last week.
- Open Air quality and check the By room table for time at 900 ppm CO₂ or more.