Troubleshooting
Quick Diagnostics
Basic Checks
Before detailed troubleshooting:
- Batteries installed correctly (polarity matched)
- LED flashed on battery installation
- Gateway operational (green blinking LED)
- Sensor within 20m of gateway or another sensor
- At least one heartbeat interval (1 hour) has passed
LED Indicators
- Single flash on power-on: Normal operation startup
- No continuous LED: Normal (battery conservation)
Note: Sensors do not have constant LED indication to maximize battery life.
Installation Issues
LED Not Flashing on Battery Installation
Symptoms:
- No LED flash when batteries inserted
- No power indication
Possible Causes:
- Batteries inserted incorrectly
- Batteries depleted or defective
- Battery contacts not making connection
- Sensor malfunction
Solutions:
Verify battery polarity
- Check +/- orientation matches compartment markings
- Both AAA batteries must be correct
- Ensure fully seated in contacts
Try fresh batteries
- Use recommended: Varta Industrial Pro 1.5V AAA LR03
- Test with multimeter: should read >1.4V per battery
- Avoid mixing old and new batteries
Check battery contacts
- Inspect for corrosion or damage
- Clean with isopropyl alcohol if needed
- Ensure spring contacts not compressed
Remove and reinsert batteries
- Take both batteries out
- Wait 10 seconds
- Reinsert with correct polarity
- Should see brief LED flash
Verify cover connection
- Ensure A-cover and B-cover properly aligned
- Press firmly until click
- Internal connection may be loose if not fully seated
If still no response: Contact support@haltian.com with sensor ID
Sensor Not Appearing in Cloud
Symptoms:
- Sensor not listed in Haltian IoT Studio
- No data received after installation
- “Last Seen” shows never or very old timestamp
Possible Causes:
- Gateway not operational
- Sensor not joined to network
- Network coverage issue (too far from gateway)
- Sensor not provisioned correctly
- First heartbeat interval not yet elapsed
Solutions:
Verify gateway operational
- Check gateway LED (should be blinking green)
- Confirm internet connectivity
- Gateway appears “Online” in IoT Studio
- Test with another known-working sensor
Confirm network coverage
- Sensor within 20m of gateway or another sensor
- Check for physical obstructions (thick walls, metal, fire doors)
- Add intermediate sensors as routers if needed
Wait for first message
- Default heartbeat: 1 hour
- First message may take 60-90 minutes
- Sensor joins network, then waits for report interval
Trigger a report manually
- Change environment significantly:
- Wave hand in front of sensor (light change)
- Warm sensor with hands (temperature change)
- Open/close nearby door if magnetic switch in use
- Should trigger event report within 5-10 minutes
- Change environment significantly:
Verify sensor provisioning
- Check sensor added to correct project in IoT Studio
- Verify sensor ID matches QR code label
- Confirm network ID and keys match gateway
Power cycle the sensor
- Remove both batteries
- Wait 30 seconds
- Reinsert batteries (correct polarity)
- LED should flash
- Wait 10 minutes for network rejoin
If still not appearing after 2 hours: Contact support with sensor ID, installation location, gateway ID, and installation time
Poor Signal Strength (RSSI)
Symptoms:
- RSSI values < -85 dBm in IoT Studio
- Intermittent data reception
- Long gaps between messages
Possible Causes:
- Sensor too far from gateway or mesh network
- Physical obstructions
- RF interference
- Suboptimal mesh density
Solutions:
Check distance to gateway
- Should be < 20m from gateway or another sensor
- Measure straight-line distance
- Account for floor height in multi-story buildings
Identify obstructions
- Metal structures, filing cabinets, equipment
- Concrete walls with rebar
- Fire doors (metal core)
- Solution: Relocate sensor or add mesh routers
Add intermediate sensors
- Deploy sensors between isolated sensor and gateway
- Each sensor acts as mesh router
- Creates redundant paths
Check for RF interference
- WiFi routers on 2.4 GHz
- Microwave ovens
- Bluetooth devices
- Solution: Relocate away from interference sources
RSSI Guidelines:
- > -60 dBm: Excellent
- -60 to -70 dBm: Good
- -70 to -85 dBm: Fair (monitor)
- < -85 dBm: Poor (action required)
Data Quality Issues
Temperature Readings Seem Incorrect
Symptoms:
- Temperature significantly different from thermostat
- Values don’t match other sensors
Possible Causes:
- Sensor in microclimate (sun, heat source, airflow)
- Comparison device inaccurate or poorly placed
- Sensor not acclimated to environment
- Normal variation due to location differences
Solutions:
Verify sensor placement
- Not in direct sunlight?
- Not near heating/cooling vents?
- Not above radiators?
- Not in cold draft from window?
- Relocate if in microclimate
Allow acclimation time
- Wait 15-30 minutes after installation or battery change
- Sensor needs to equilibrate to room temperature
Compare to calibrated reference
- Thermostat may be in different location (different temperature)
- Thingsee ENVIRONMENT: ±0.3°C accuracy
- 2-3°C variation normal in same room
Check for thermal sources
- Sun exposure (even indirect)
- Nearby equipment (computers, monitors)
- Heat from lighting
- Solution: Relocate to representative location
If readings still seem incorrect: Document exact values, comparison device specs, installation location. Contact support for sensor verification.
Humidity Readings Seem Wrong
Symptoms:
- Humidity significantly different from other devices
- Values seem too high or too low
Possible Causes:
- Consumer comparison device inaccurate (±5-10% typical)
- Sensor in microclimate (near bathroom, kitchen, humidifier)
- Recent battery change (sensor needs recalibration time)
- Sensor exposed to condensing humidity
Solutions:
Verify comparison device accuracy
- Consumer humidity meters often inaccurate
- Thingsee ENVIRONMENT: ±5% RH accuracy
- Use NIST-traceable reference if available
Check sensor location
- Not near bathroom or kitchen (high humidity)
- Not near humidifier or dehumidifier
- Not in direct HVAC airflow
- Relocate if in microclimate
Wait for stabilization
- After battery change, wait 1-2 hours
- After exposure to condensing humidity, wait 4-6 hours for sensor recovery
Verify no condensation exposure
- Humidity sensor degrades if exposed to condensing conditions
- IP30 rating: Not suitable for wet environments
- If condensation occurred, contact support for sensor evaluation
Ambient Light Readings Fluctuate or Seem Incorrect
Symptoms:
- Light values don’t match expectations
- Readings fluctuate wildly
- Doesn’t detect lights on/off
Important: Light sensor is not calibrated - provides indicative values only
Possible Causes:
- Sensor orientation (not facing light sources)
- Shadows or obstructions blocking sensor
- Daylight overwhelming artificial light
- Normal behavior (sensor designed for on/off detection, not precision)
Solutions:
Understand sensor limitations
- Light measurement indicative only
- Suitable for relative changes and on/off detection
- Not suitable for precision lux measurements
Check sensor orientation
- Sensor face should point toward room lights
- Not obstructed by furniture or equipment
- Not in shadow
Verify light source detection
- Turn lights fully on → expect 300-1000+ lux
- Turn lights fully off → expect < 50 lux
- Large difference confirms working
Consider daylight interference
- Near windows: daylight may overwhelm room lights
- Use higher threshold (e.g., 10,000 lux) to detect major changes
- Or relocate sensor away from window influence
Expected behavior: Large changes (thousands of lux) when lights turn on/off. Absolute values less important than relative changes.
Magnetic Switch Not Detecting Door/Window Opens
Symptoms:
- State counter not incrementing
- Door opens but no detection in IoT Studio
- Inconsistent detection
Possible Causes:
- Magnet and sensor not aligned
- Gap too large (> 15mm)
- Wrong magnet type (too weak)
- Magnet orientation incorrect
Solutions:
Verify alignment
- Sensor and magnet must be parallel, facing each other
- Maximum gap when closed: 15mm (preferably 5-10mm)
- Use ruler to measure gap
Check magnet strength
- Use strong permanent magnet (neodymium recommended)
- Test: Magnet should attract small metal objects
- Weak magnets may not trigger sensor
Test magnet orientation
- Magnet has north and south poles
- Try flipping magnet 180° if detection poor
- One orientation typically works better
Verify sensor sees magnet
- With door/window closed, magnet should be directly adjacent to sensor
- Move magnet closer if gap too large
- Check that door/window doesn’t sag or shift when opening/closing
Test detection
- Slowly open door/window while watching IoT Studio
- Counter should increment within 1-5 minutes
- Perform several open/close cycles to confirm consistent detection
If still not working: Magnet may be too weak, or gap too large. Contact support for replacement magnet or troubleshooting assistance.
Machine Usage Mode Not Detecting Vibration
Symptoms:
- Equipment running but no vibration reports
- Machine Usage Mode enabled but no data
- Accelerometer shows static values only
Possible Causes:
- Machine Usage Mode not actually enabled (contact support required)
- Insufficient vibration (below 128mG threshold)
- Poor mechanical coupling (tape mounting on vibrating equipment)
- Equipment not actually running during test
Solutions:
Verify Machine Usage Mode enabled
- Contact Haltian support to confirm configuration
- Standard mode does NOT detect vibration (only position/orientation)
- Support must remotely enable Machine Usage Mode
Check mounting method
- Must use screw mounting for vibration detection
- Tape mounting insufficient (dampens vibration)
- Ensure rigid mechanical coupling to equipment
- Verify screws tight (no wobbling)
Verify equipment vibration level
- Some equipment has very low vibration (< 128mG threshold)
- Test by touching equipment - should feel vibration clearly
- If barely perceptible, may be below detection threshold
- Contact support to lower threshold if needed
Confirm equipment actually running
- Verify equipment in operating mode (not idle)
- Run full operational cycle during test
- Check that vibration present at sensor location
Check sensor orientation and location
- Vibration strongest at certain points on equipment
- Try different mounting location if possible
- Ensure sensor not on dampened/isolated part
If still not detecting: Contact support with equipment type, mounting details, and approximate vibration level. Support can verify Machine Usage Mode configuration and adjust sensitivity.
Battery Issues
Battery Life Shorter Than Expected
Symptoms:
- Battery level dropping faster than 5-year expected life
- Frequent low battery warnings
- Battery depleted in < 3 years
Possible Causes:
- High reporting frequency (custom configuration)
- Machine Usage Mode (expected 4 years vs. 5 years standard)
- Poor signal strength (many retransmissions)
- Sensor acting as mesh router for many others
- Low-quality or old batteries
- Cold operating environment
Solutions:
Review configuration
- Check reporting thresholds and intervals in IoT Studio
- Very low thresholds = frequent reports = more battery use
- Machine Usage Mode uses more power (50Hz sampling when active)
- Default thresholds optimal for battery life
Improve signal strength
- Poor RSSI (< -85 dBm) causes retransmissions
- Add intermediate sensors to improve mesh
- Better signal = less power per transmission
Check mesh network density
- If sensor routing for many others, power consumption higher
- Contact support for network topology review
Verify battery quality
- Use recommended: Varta Industrial Pro 1.5V AAA LR03
- Avoid bargain or off-brand batteries
- Check expiration date
- Old batteries (> 2 years in storage) have reduced capacity
Operating temperature
- Cold environments reduce battery capacity
- Alkaline batteries lose capacity below +10°C
- Shorter battery life expected in cold areas
Battery life estimates:
- Standard mode (default): 5 years
- Machine Usage Mode: 4 years
- High-frequency custom config: 3-4 years
Low Battery Warning but Batteries Recently Replaced
Symptoms:
- Low battery alert shortly after new batteries
- Battery level drops rapidly from 100%
Possible Causes:
- Batteries not fresh (old stock)
- Poor quality batteries
- Battery contacts not making good connection
- Very cold environment affecting measurement
Solutions:
Verify battery freshness
- Check expiration date on battery packaging
- Batteries have ~2-3 year shelf life
- Old stock may have reduced capacity
Test battery voltage
- Use multimeter: should read 1.5-1.6V per battery when fresh
- < 1.4V indicates depleted or defective
Try different battery brand
- Use recommended: Varta Industrial Pro AAA
- Alkaline batteries required (not lithium, not rechargeable)
Clean battery contacts
- Remove batteries
- Clean contacts with isopropyl alcohol
- Ensure spring contacts not damaged
- Reinsert fresh batteries
Check environmental temperature
- Battery level calculation affected by extreme cold
- Below +10°C, apparent capacity reduces
- If sensor in cold zone, indication may be pessimistic
Wait 24 hours
- Battery level calculation may need time to stabilize
- If drops to < 20% within 24 hours, batteries defective
If issue persists: Try completely different battery batch. Contact support with sensor ID and battery details.
Network and Connectivity Issues
Sensor Reporting Intermittently
Symptoms:
- Gaps in data (missing hours or days)
- “Last Seen” timestamp irregular
- Messages arrive in bursts, then silence
Possible Causes:
- Borderline signal strength (RSSI near -85 dBm)
- Gateway intermittent connectivity or reboots
- Temporary RF interference
- Mesh network instability
Solutions:
Check signal strength trends
- Review RSSI history in IoT Studio
- If hovering around -85 dBm, borderline coverage
- Add intermediate sensor to improve link
Verify gateway stability
- Check gateway uptime and connectivity
- Gateway reboots cause temporary sensor silence
- Review gateway logs for issues
Monitor for patterns
- Do gaps occur at specific times? (interference)
- Random gaps or consistent time of day?
- Pattern may indicate external cause
Add mesh redundancy
- Deploy additional sensors in area
- Creates multiple routing paths
- Improves network resilience
Review mesh network health
- Contact support for network analysis
- Identify routing bottlenecks or weak links
Expected behavior:
- Continuous reports every 5-60 minutes (depending on activity)
- Maximum gap: heartbeat interval (default 1 hour)
- Occasional 2-hour gap acceptable
- Gaps > 3 hours indicate problem
No Data After Battery Replacement
Symptoms:
- Sensor was working, stopped after battery change
- LED flashed on new battery installation
- But no data in cloud
Possible Causes:
- Sensor not rejoined to network after reboot
- Batteries inserted incorrectly despite LED flash
- Configuration reset (rare)
Solutions:
Wait for network rejoin
- After battery replacement, sensor reboots
- Network rejoin: 1-10 minutes
- First data may arrive after heartbeat (up to 1 hour)
- Be patient, wait 1-2 hours
Verify batteries correctly installed
- Double-check polarity markings
- Both batteries correctly oriented
- LED flash doesn’t guarantee proper operation if one battery reversed
Power cycle again
- Remove both batteries
- Wait 30 seconds
- Reinsert carefully (correct polarity)
- Wait 1 hour for first report
Check IoT Studio device list
- Sensor should still be listed
- If missing, may need reprovisioning
- Contact support if device disappeared
Trigger event manually
- Wave hand in front (light change)
- Warm sensor (temperature change)
- Should trigger event report within 5-10 minutes
If still no data after 2 hours: Contact support - sensor may need reprovisioning (rare)
Support and Diagnostics
Collecting Diagnostic Information
When contacting support, provide:
Sensor Information:
- Sensor ID (from QR code label)
- Installation date
- Physical location description
- Battery installation/replacement dates
- Operational mode (Standard or Machine Usage)
Symptom Details:
- What is not working as expected?
- When did issue start?
- Recent changes (batteries, moved sensor, configuration)?
- How frequently does issue occur?
IoT Studio Data:
- Last seen timestamp
- Recent RSSI values
- Battery level
- Screenshot of sensor dashboard if possible
Environmental Context:
- Room size and type
- HVAC system (always on, scheduled, none)
- For Machine Usage Mode: Equipment type, expected vibration level
- For magnetic switch: Door/window type, magnet position
Contacting Support
- Email: support@haltian.com
- Subject line: “Thingsee ENVIRONMENT - [brief issue description]”
- Provide: Sensor ID, symptom, troubleshooting attempted
- Response time: Typically within 1 business day
Warranty and Replacement
- Standard warranty: 2 years from purchase date
- Exclusions: Battery depletion, physical damage, environmental damage
- RMA process: Contact support for return authorization
- Replacement timeline: Typically 1-2 weeks
Preventive Maintenance
Regular Checks (Monthly)
- Verify sensor reporting in IoT Studio
- Check battery level (should decline slowly)
- Review RSSI signal strength
- Spot-check measurement values for reasonableness
- If magnetic switch: Test door/window detection
Periodic Maintenance (Annually)
- Visual inspection (physical damage?)
- Verify mounting still secure
- Clean sensor exterior with dry cloth (dust)
- Review historical data trends
- Verify placement still optimal (room layout changes?)
Battery Replacement Planning
- Schedule replacement at 20% battery level
- Keep spare AAA batteries in inventory
- Use recommended: Varta Industrial Pro 1.5V AAA LR03
- Document replacement dates for lifecycle tracking
Related Documentation
- Installation Guide - Proper installation procedures
- Operation Guide - Normal operation and data interpretation
- Configuration Guide - Parameter customization
- Specifications - Technical details
Still having issues? Contact support@haltian.com with your sensor ID and problem description.